MM100 Specification Micro-Ohm Meter - Microhm Tester with 100 / 1200A Output Print E-mail
MEASUREMENT OUTPUT
Current:

Pulsed 1200A DC maximum (at 4V) dependant on loop impedance. Pulsed / continuous 100A DC regulated (up to 6V).

No-Load Voltage:10V DC maximum.
Operation:

1200A pulse with 1 second duration.

100A pulse with 2 second duration.

100A continuous (no time limit).

Safety:

Re-settable thermal / magnetic circuit breaker.

Connectors:Heavy duty wing-nut.

MEASUREMENT INPUT

 
Range:0 to 1.999 or 19.99mΩ (selectable).
Resolution:1 or 10µΩ (range selected).
 1% of reading +/- 1 digit.
Voltage Sense:1 x voltage input from contact / joint.
Connectors:4mm safety socket.
OUTPUTS 
Analogue:3 x 0 to 10V DC conditioned outputs representing measured Voltage Drop, Current Level and Microhms. 1 x Calibrate for calibration check.
Connectors:1 x Calibrate for calibration check.
GENERAL SYSTEM 

Back-lit 3½ digit LCD for readout of Ohms or Amps (switch selectable). Current On lamp indication (red). Unit Armed lamp indication (green). Trigger In (volt free contact) for Dynamic Microhm Test (SA100 required) and Trigger Out (15V logic). Intermittent audible during continuous operation.

Operate’ push button for 100 / 1200A pulse or 100A continuous with stop, modes of operation (static testing). Rotary selector switch for Off / 100A (1.999mΩ range) / 100A (19.99mΩ range) / 1200A (1.999mΩ range). LED indicators for Fault, Over Current, Battery Low and Charging. Multipurpose accessory socket for in-car charging, remote meter, power out, trigger in and trigger out.

OPERATING VOLTAGES 
Prime Power:Internal sealed rechargeable batteries.
Recharge Power:

100 to 350V DC, 88 to 264V AC, In-Car 12V DC @ 3A (negative earth).

Burden:<100VA load.
ENVIRONMENTAL 

Operating Temperature:

-20ºC to 55ºC (-4ºF to 131ºF).
Humidity:0 to 97% RH non-condensing.
Isolation:2kV rms for 1 minute (input / output to ground).

Surge Withstand Transient:

To IEC 801-5. 5kV, 1.2/50mSec, 0.5 joule. Common Mode: Severity level class 4. Series Mode: Severity level class 3.

RF Immunity: To IEC 801-3 level 3. 10V/m 26-1000MHz.
Emissions:To EN50081-1: 1992.
MECHANICAL DETAILS 
Case:

500mm wide.

330mm high.

380mm deep.

Weight: 19.6kg.