MEASUREMENT OUTPUT

Current
100 or 200A DC regulated (up to 4V).
No-Load Voltage
10V DC maximum.
Operation
100A pulse with adjustable on-time.
200A pulse with adjustable on-time.
100A continuous (no time limit).
200A continuous (no time limit).
SafetyRe-settable thermal / magnetic circuit breaker.
Connectors
Heavy duty wing-nut.

MEASUREMENT INPUT

Range:
0 to 199.9μΩ or 0 to 1999μΩ.
Resolution:
0.1 or 1μΩ (range dependant).

1% of reading +/- 1.
Voltage Sense:
1 x voltage input from contact / joint.
Connectors:4mm safety socket.

OUTPUT

Analogue:
2 x conditioned outputs representing measured Current Level and Micro- Ohms (SA100, SA100R or SA100RS required).
1 x Calibrate for calibration check.
Connectors:
4mm safety socket.

GENERAL SYSTEM

Back-lit 31⁄2 digit LCD for readout of μΩ or Amps.
Current On lamp indication (red).
Unit Armed lamp indication (green).
Trigger In (volt free contact) for Dynamic Micro-Ohm Test (SA100, SA100R or SA100RS required) and Trigger Out (15V logic).

Intermittent audible during continuous operation.
Typical full charge performance: 100A for 35 minutes. ‘Operate’ push button for Pulse mode or Continuous with stop mode of operation.

Rotary Mode selector switch for Off / 100A / 200A.
Rotary Range selector switch for 199.9μΩ or 1999μΩ.
Rotary Pulse On-Time selector switch for 0.125s, 0.25s, 0.5s, 1s or 2s.
LED Indicators: Fault, Over Current, Over Temperature, Battery Low and Charging.
Multipurpose accessory socket for in-car charging, remote meter, power out, trigger in and trigger out.

OPERATING VOLTAGES

Prime Power:
Internal sealed rechargeable batteries.
Recharge Power:
110 to 330V DC or 85 to 265V AC (47
to 440Hz) auto-sensing.
In-Car 12V DC @ 3A (negative earth).
Burden:
<100VA load.

ENVIRONMENTAL

Operating
Temperature:

-20oC to 70oC (-4oF to 158oF).
Humidity:
0 to 97% RH non-condensing.
Isolation:
2kV rms for 1 minute (input / output to ground).
Surge Withstand Transient:
To IEC 801-5. 5kV, 1.2/50μSec, 0.5 joule.
Common Mode: Severity level class 4.
Series Mode: Severity level class 3.
RF Immunity:
To IEC 801-3 level 3.
10V/m 26-1000MHz.
Emissions:To EN50081-1: 1992.

MECHANICAL DETAILS

Case:
Reinforced aluminium, 370mm wide x 185mm deep x 350mm high.
Weight:
<10kg.

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE