OUTPUTS
AC Current:0 to 10A range with the following characteristics:-
 

No-Load Voltage (min.): 80V

Full-Load Voltage (min.): 70V

Full-Load Current (max.): 10A

Time: 2 hours

Safety: Output transformer equipped with built-in temperature protection.

Primary side protected by miniature circuit breakers.

0 to 25A range with the following characteristics:-

No-Load Voltage (min.): 24V

Full-Load Voltage (min.): 20V

Full-Load Current (max.): 25A

Time: 1 hour

Safety: Output transformer equipped with built-in temperature protection.

Primary side protected by miniature circuit breakers.

 

0 to 50A (short term max. 200A peak) range with the following characteristics:-

No-Load Voltage (min.): 10V

Full-Load Voltage (min.): 2V

Full-Load Current (max.): 50A

Time: 1.5 minutes

Safety: Output transformer equipped with built-in temperature protection.

Primary side protected by miniature circuit breakers.

AC/DC Voltage: 0 to 240V AC rated at 2A for 1 hour.

0 to 300V DC rated at 2A for 1 hour.

Auxiliary Voltage: 240V AC rated at 0.5A.

240V AC rated at 0.5A. 110V DC rated at 0.5A, 110V AC rated at 0.5A & 30V DC rated at 1A.

If the 110V DC & AC fixed outputs are used simultaneously the rating is 0.2A each.

Safety (Voltage): Re-triggerable fuses used in all voltage outputs

INPUTS 
Digital:2 x wet contacts and 1 x dry contact.
  
TIMER 
Range:0.000 to 999.999 seconds, auto-ranging.
Resolution:1mSec.
Max. Testing Time:999.999 seconds.
MEASUREMENTS 
Readout:

Output parameters are displayed on a large backlit LCD display.

Auto-ranging if output is less than 10% of range.

Measured Quantities:

AC current output.

Timer.

Accuracy:±0.5% of metering.
AC Measurement:True RMS.
Set of Resistors: 0.5Ω (10A max.), 1Ω (5A max.), 25Ω (2A max.), 100Ω (0.7A max.) & 500Ω (0.3A max.).
OPERATING VOLTAGES 
Prime Power:230 or 115V AC ±15%, 50/60Hz.
ENVIRONMENTAL 

Operating

Temperature:

-20ºC to +70ºC

Storage

Temperature:

-40ºC to +70ºC

MECHANICAL DETAILS  
Weight:10kg.
Carry Case:Reinforced aluminium, 13.5” x 9.5” x 6” (340mm x 240mm x 150mm).
  